Desiccant Rotor Dehumidifier with AHU ZCB-5000
Category:
DESCRIPTION
- It can accurately meet the user's requirements for temperature and relative humidity.
- The use of imported super silica gel runners from Sweden has high dehumidification efficiency and long service life. The relative humidity of the supply air is RH ≤ 20%, and the dew point temperature can reach TL ≤ -20 ° C.
- High-strength anti-cold bridge high-quality aluminum alloy frame structure
- The box module adopts the internationally popular modular design, double-layer high-quality Baosteel color steel plate, filled with disposable high-density polyurethane foam molding.
- Electrical control uses PLC automatic control, touch screen human-machine interface
- The unit's water receiving tray and bottom inner plate are made of 304 stainless steel, which is sturdy and durable, and is corrosion-resistant and rust-proof.
- Recycling process adopts unique heat recovery and energy saving technology
- Regenerative heating electricity, steam, heat-conducting oil, natural gas are optional; multiple heating methods can be used for switching.
Technical Parameters
Main Parameters Item |
ZCB-D/Z -2000 |
ZCB-D/Z -3000 |
ZCB-D/Z -4000 |
ZCB-D/Z -5000 |
ZCB-D/Z -6000 |
ZCB-D/Z -8000 |
ZCB-D/Z -10000 |
ZCB-D/Z -12000 |
ZCB-D/Z -15000 |
ZCB-D/Z -20000 |
ZCB-D/Z -25000 |
|||
Process Airflow |
m3/h |
2000 |
3000 |
4000 |
5000 |
6000 |
8000 |
10000 |
12000 |
15000 |
20000 |
25000 |
||
Reactivation Airflow |
m3/h |
670 |
1000 |
1330 |
1670 |
2000 |
2670 |
3330 |
4000 |
5000 |
6670 |
8350 |
||
Supply Air Parameters |
/ |
T=15-25℃, RH=10%-30% |
||||||||||||
Reactivation Consumption |
Electric |
kw |
18 |
24 |
30 |
36 |
42 |
60 |
72 |
96 |
120 |
156 |
198 |
|
Steam |
kg/h |
30 |
45 |
60 |
75 |
90 |
110 |
140 |
170 |
215 |
285 |
360 |
||
Steam Pipe |
mm |
DN20 |
DN20 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN25 |
DN32 |
DN32 |
||
Chilled Water Temperature |
℃ |
T≤7℃ |
||||||||||||
Chilled Water Consumption |
T/h |
5 |
10 |
12 |
15 |
20 |
25 |
30 |
35 |
45 |
60 |
75 |
||
Diameter of Chilled Water Pipe |
mm |
DN40 |
DN40 |
DN40 |
DN50 |
DN50 |
DN50 |
DN65 |
DN65 |
DN65 |
DN80 |
DN80 |
||
Reactivation Fan Power |
kw |
0.75 |
1.1 |
1.1 |
1.5 |
1.5 |
2.2 |
2.2 |
3.0 |
5.5 |
5.5 |
7.5 |
||
Process Fan Power |
kw |
2.2 |
3.0 |
4.0 |
5.5 |
5.5 |
7.5 |
11 |
11 |
15 |
18.5 |
22 |
||
Driving Motor Power |
kw |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.2 |
0.2 |
0.2 |
0.2 |
0.2 |
||
Power Supply |
3P-380V-50HZ Three-phase four-wire system |
|||||||||||||
Installed Power |
Electric Mode |
kw |
21.05 |
28.2 |
35.2 |
43.1 |
49.1 |
69.8 |
85.4 |
110.2 |
140.7 |
180.2 |
227.7 |
|
Steam Mode |
kw |
3.05 |
4.2 |
5.2 |
7.1 |
7.1 |
9.8 |
13.4 |
14.2 |
20.7 |
24.2 |
29.7 |
||
Diameter of Fresh Air Inlet |
mm |
250×200 |
320×250 |
400×250 |
500×250 |
500×320 |
630×320 |
800×320 |
800×400 |
1000×400 |
1000×500 |
1250×500 |
||
Diameter of Reflow Air Inlet |
mm |
250×200 |
320×250 |
400×250 |
500×250 |
500×320 |
630×320 |
800×320 |
800×400 |
1000×400 |
1000×500 |
1250×500 |
||
Diameter of Supply Air Outlet |
mm |
400×250 |
500×320 |
630×320 |
800×320 |
800×400 |
800×500 |
1000×500 |
1000×630 |
1250×630 |
1250×800 |
1600×800 |
||
Diameter of Reactivation Air Inlet |
mm |
400×300 |
550×350 |
550×400 |
550×450 |
650×450 |
750×500 |
750×550 |
800×500 |
800×550 |
850×550 |
850×650 |
||
Diameter of Reactivation Air Outlet |
mm |
160×125 |
208×162 |
208×162 |
233×183 |
233×183 |
260×228 |
262×204 |
262×204 |
302×234 |
332×257 |
487×340 |
||
Surplus Pressure of the Unit |
Pa |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
≥650 |
||
Overall Dimension |
L |
mm |
5200 |
5200 |
5200 |
5700 |
5700 |
5850 |
5850 |
6000 |
6200 |
6250 |
6500 |
|
W |
mm |
800 |
900 |
1000 |
1100 |
1200 |
1300 |
1400 |
1500 |
1700 |
1900 |
2100 |
||
H |
mm |
1200 |
1300 |
1400 |
1500 |
1600 |
1700 |
1850 |
2000 |
2200 |
2400 |
2600 |
||
Weight |
kg |
1150 |
1450 |
1600 |
1800 |
2000 |
2200 |
2400 |
2700 |
2800 |
3200 |
3500 |
Recommended products